Outside Diameters and Wall Thicknesses For CPVC 4120, SDR 11 Plastic Pipe As Per ASTM D-2846

Nominal Size

(in.)   (mm)  

Outside Diameter, in. (mm) Wall Thickness, in. (mm)  Pressure Ratting. PSI (Kg.Cm²)
Avarage Tolerance Minimum Tolerance 73.4°F           (23°C) 180°F           (82°C)
½*         (15) 0.625 (15.9) ± 0.003 (0.08) 0.068 (1.73) +0.020 (0.51) 400 (28.1) 100 (7.0)
¾           (20) 0.875 (22.2) ± 0.003 (0.08) 0.080 (2.03) +0.020 (0.51) 400 (28.1) 100 (7.0)
1            (25) 1.125 (28.6) ± 0.003 (0.08) 0.102 (2.59) +0.020 (0.51) 400 (28.1) 100 (7.0)
1¼         (32) 1.375 (34.9) ± 0.003 (0.08) 0.125 (3.18) +0.020 (0.51) 400 (28.1) 100 (7.0)
1½         (40) 1.625 (41.3) ± 0.004 (0.10) 0.148 (3.76) +0.020 (0.51) 400 (28.1) 100 (7.0)
2           (50) 2.125 (54.0) ± 0.004 (0.10) 0.193 (4.90) +0.023 (0.58) 400 (28.1) 100 (7.0)

* For ½” wall thickness minimum is not a function of SDR.